Goodman AC is a popular air conditioning brand that has been providing reliable and efficient cooling solutions for households and businesses for several years. With its commitment to innovation and quality, Goodman has become a trusted name in the air conditioning industry, offering a wide range of air conditioning products to meet the needs of different customers.
Below you can find the list of Error Codes for Goodman AC
Tags: #Goodman, #GoodmanAC, #GoodmanACErrorCodes
Error Codes | Problem |
---|---|
A2 | Shorted sensor./Open sensor./Sensor disconnected./Sensor out of range. |
A3 | Shorted sensor./Open sensor./Sensor disconnected./Sensor out of range. |
E5 | Short in low voltage wiring. |
EE | Compressor relay contacts welded. |
b0 | Indoor blower motor problem./Communications errorbetween indoor and outdoor unit. |
b9 | Indoor blower motor problem./Blocked filters./Restrictive/ undersized ductwork./Indoor-outdoor unit miss match. |
d0 | Air conditioner/heat pump is wired as part of a communicating system and integrated control module does not contain any shared data. |
d1 | Air conditioner/heat pump is wired as part of a communicating system and integrated control module contains invalid shared data or network data is invalid for the integrated control module. |
d2 | Air conditioner/heat pump is wired as part of a communicating system and outdoor unit requires airflow greater than indoor unit’s airflow capability./ Shared data is incompatible with the system or missing parameters. |
d3 | Shared data sent to integrated control module does not match hardware configuration. |
d4 | Shared data on memory card has been rejected. |
01 | Low refrigerant charge./Restriction in liquid line./Indoor blower motor failure.Indoor thermostat set extremely low. |
02 | Blocked condenser coil./Outdoor fan not running. |
03 | Intermittent thermostat demand./Faulty compressor relay. |
04 | Compressor bearings are seized./Failed compressor run capacitor./Faulty run capacitor wiring./Faulty compressor wiring./Low line voltage. |
05 | Power is disconnected./Failed compressor protector./Compressor not properly wired to control. |
06 | Compressor start winding is open./Failed compressor run capacitor./Faulty run capacitor wiring./Compressor not properly wired to control./Faulty compressor wiring. |
07 | Compressor run winding is open./Compressor no properly wired to control./Faulty compressor wiring. |
08 | Low line voltage./ High line voltage. |
09 | Control detects secondary voltage less than 18 VAC./Transformer overloaded./Low line voltage. |